Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15CM05730
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2017 | FIRE - ALARM FINAL | Approved | ||
12/01/2016 | FIRE - ALARM FINAL | Partial Approval | 1. Tested panic door delay. All verified. 2. Waiting on revised Fire Alarm plans. |
|
11/30/2016 | FIRE - ALARM FINAL | Partial Approval | 1. Tested all duct detectors. All verified. 2. Tested 3 Kitchen Hoods. All verified. 3. Need to verify panic delay when installed. 4. Waiting on As builds from Climatec. |
|
11/14/2016 | FIRE - ALARM FINAL | Partial Approval | Need to test the kitchen ansul systems. Tested via the microswitch. Need to test the duct smoke detectors for proper shut down. Need to test the ground fault monitoring. Request AsBuilt drawings from Climatec. Need to verify the panic delay once it is installed. Verified monitoring via cellular unit. Water flow and tamper ditinct signals. Tamper switches verified. Manual pull station verified. Smoke's above the panels verified. |