Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/09/2015 |
FIRE - FINAL |
|
Approved |
|
| 12/07/2015 |
FIRE - FINAL |
|
Partial Approval |
FIRE CODE OFFICIAL IS OKAY WITH A TEMPORARY OCCUPANCY FOR EMPLOYEE TRAINING IF GRANTED BY THE BUILDING DEPARTMENT. PUBLIC OCCUPANCY WILL NOT BE ALLOWED UNTIL ALL ITEMS ARE CORRECTED (PANIC HARDWARE INSTALLED PER APPROVED PLANS ON SHEET A-1 REVISION DATE OF 10-8-15) KEN BROUILLETTE. |
| 12/04/2015 |
FIRE - FINAL |
|
Denied |
1) Need panic hardware on 2nd exit door. The main doors have panic but aren't required to have panic. All secondary exits require panic hardware. IFC 1008.1.10 & IFC 1008.1.9.3 #2. Only the main door can have locking hardware that is not panic. |