Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM05668
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2015 | FIRE - FINAL | Approved | ||
12/07/2015 | FIRE - FINAL | Partial Approval | FIRE CODE OFFICIAL IS OKAY WITH A TEMPORARY OCCUPANCY FOR EMPLOYEE TRAINING IF GRANTED BY THE BUILDING DEPARTMENT. PUBLIC OCCUPANCY WILL NOT BE ALLOWED UNTIL ALL ITEMS ARE CORRECTED (PANIC HARDWARE INSTALLED PER APPROVED PLANS ON SHEET A-1 REVISION DATE OF 10-8-15) KEN BROUILLETTE. | |