Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T15CM05193
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2015 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
10/02/2015 | ELECTRIC - RECONNECT | Denied | 1 SUPPORT CONDUIT AROUND SERVICE PANEL 2 MISSING DEADFRONT COVER ON SERVICE PANEL 3 MISSING COVER FOR 240V RECEPT 4 PROVIDE PERMIT PLANS FOR ENCLOSED ADDITION ON SOUTH SIDE OF HOUSE 5 INSTALL SMOKE DETECTORS IN ALL BEDROOMS 6 WIRES/FEEDERS TO NEW SUB PANEL NOT CORRECT COLOR CODE, HOW DID YOU INSTALL WIRING TO SUB PANEL? 7 PLUG UNUSED OPENINGS IN SERV PANEL 8 SERVICE PANEL NEEDS MAIIN CKT BREAKER SEE NOTES LAST INSPECTION |
|
07/29/2015 | ELECTRIC - RECONNECT | Denied | CONSULT QUALIFIED LICENSED ELECTRICAN FOR REPAIRS |