Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2016 | FIRE - FINAL | Approved | ||
| 12/14/2015 | FIRE - FINAL | Denied | 1. Both exit signs need to be battery back type as per the approved plans on PG. E1 2. Need to repair or replace one smoke detector was beeping when inspection was being completed 3. Insulate orange pipe sticking out of the ground for the fire sprinkler underground must keep it from freezing 4. Protect orange piping for fire sprinkler from damage 5. Need two 2A-10BC type fire extinguishers 6. Need exit escape plans in each room and hallways 7. Need to have sprinkler contractor to call in on their permit for finals T15BU00944 |