Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2015 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 08/05/2015 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/05/2015 | ELECTRIC - RECONNECT | Denied | INSTALL SMOKE DETECTORS WITH TWO SCREWS. REMOVE ALL WIRING TO PATIO FLOOD LIGHTS OR WIRE TO CODE. REMOVE THE TEMPERATURE CONTROLLER AT POOL PUMP OR WIRE TO CODE. PROPERLY SECURE THE DEADFRONT AT PANEL. THE LB IN CIRCUIT TO POLE LIGHT IN FRONT YARD NOT APPROVED FOR DIRECT BURIAL. AND EMT NOT APPROVED FOR DIRECT BURIAL | |
| 07/29/2015 | ELECTRIC - RECONNECT | Not ready for Inspection | 1. PROVIDE ACCESS TO THE ELECTRIC PANEL ON THE BACK SIDE OF HOUSE. PANEL IS COMPLETELY BLOCKED BY 7' HIGH SHRUBS. |