Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2017 | ELECTRIC - FINAL | Approved | APPROVED DGC | |
| 11/28/2017 | ELECTRIC - FINAL | Denied | LOOSE BOND BUSHING ON METER BASE BOTTOM. MISSING BOND BUSHING AT METER BASE INLET |
|
| 11/24/2017 | ELECTRIC - FINAL | Denied | MISSING BOND BUSHING AT DISCONNECT AND MAIN PANEL SOLAR BREAKER MUST BE AT THE FURTHEST POSITION AT THE BUS BAR FROM THE BREAKER WIRE SIZES DO NOT MATCH PLAN DISCONNECT ON ROOF IS NOT SHOWN ON PLANS |