Permit: T15CM04856

Parcel: 13307017A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/20/2015 ELECTRIC - FINAL Approved RECOMMEND SERVICE UPGRADE AND RACEWAYS TO SUB. PANELS OR DISCONECTS
08/19/2015 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/29/2015 ELECTRIC - FINAL Denied REMOVE LIGHT FIXTURE AT MASTER BEDROOM or wire per code. you cannot use romex a cord and plug light fixture.remove the power cords from under living room book shelf. replace broken receptacle in master bedroom. properly identify neutral conductor at disconnect. remove all exposed romex to outdoor kitchen or wire per code. all outdoor receptacles must be gfi. remove all electric components to porch light rear of house. any splice must be in a j box. remove any exposed wiring at a/c unit or wire per code. provide access to a/c unit. recommend a licensed electrician do the work.
list may not be complete