Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T15CM04797
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/21/2015 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/21/2015 | ELECTRIC - FINAL | Partial Approval | PANEL BUSS IS RATED FOR 200 AMPS. A 60 AMP BACKFEED BREAKER OVERLOADS TH BUSS. REVISE PLANS AND DERATE MAIN BREAKER AS NECESSARY. DEADFRONT DOESN'T FIT PANEL PROPERLY. EVERYTHING ELSE IS OK |