Permit: T15CM04753

Parcel: 138143120

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/14/2015 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/14/2015 ELECTRIC - SERVICE UPGRADE Approved 1. SCHEDULE FOR RECONNECT INSPECTION
2. PROVIDE ACCESS FOR RECONNECT INSPECTION. BE SURE TO FOLLOW THE COT RECONNECT REQUIREMENTS
3. CLEARANCE FOR POWER UPON RECONNECT APPROVAL. DWELLING UNOCCUPIED AT THIS TIME
08/13/2015 ELECTRIC - SERVICE UPGRADE Denied 1. SUPPORT #4 BARE GROUND TO BUILDING STRUCTURE. THE ONE GOING ACROSS THE PATIO IS A TRIP HAZARD. MUST BE ENCASED OR BELOW CONCRETE
2. RISER CONDUIT NOT SUPPORTED PER CODE. STRAP TO BUILDING STRUCTURE WITH APPROVED STRAPS
3. PLUG UNUSED OPENINGS IN DEADFRONT COVER
4. ID CIRCUIT BREAKERS
5. RISER CONDUCTORS TO BE 4/0 IF ALUM, 2/0 IF COPPER
6. MISSING WEATHER HEAD