Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2015 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/14/2015 | ELECTRIC - SERVICE UPGRADE | Approved | 1. SCHEDULE FOR RECONNECT INSPECTION 2. PROVIDE ACCESS FOR RECONNECT INSPECTION. BE SURE TO FOLLOW THE COT RECONNECT REQUIREMENTS 3. CLEARANCE FOR POWER UPON RECONNECT APPROVAL. DWELLING UNOCCUPIED AT THIS TIME |
|
| 08/13/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. SUPPORT #4 BARE GROUND TO BUILDING STRUCTURE. THE ONE GOING ACROSS THE PATIO IS A TRIP HAZARD. MUST BE ENCASED OR BELOW CONCRETE 2. RISER CONDUIT NOT SUPPORTED PER CODE. STRAP TO BUILDING STRUCTURE WITH APPROVED STRAPS 3. PLUG UNUSED OPENINGS IN DEADFRONT COVER 4. ID CIRCUIT BREAKERS 5. RISER CONDUCTORS TO BE 4/0 IF ALUM, 2/0 IF COPPER 6. MISSING WEATHER HEAD |