Permit: T15CM04717

Parcel: 111070790

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T15CM04717

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2015 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/10/2015 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
07/20/2015 ELECTRIC - FINAL Not ready for Inspection ALL BLDG PENETRATIONS ARE REQUIRED TO BE WEATHER TIGHT. REFER TO INSTALL INSTRUCTIONS. PROVIDE ACCESS INSIDE. WTR HTR IS OK
07/16/2015 ELECTRIC - FINAL Not ready for Inspection SECURE CONDUIT CONNECTORS SEAL AROUND OUTLET BX
PROVIDE TYPE B VENT TO TERMINATION
PROVIDE CLEARANCE AND PROPER SUPPORT
PROVIDE NEW FLEX and sediment trap