Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2016 | FIRE SPKLR - FINAL | Approved | ||
| 02/17/2016 | FIRE SPKLR - FINAL | Partial Approval | Still need alarm final. | |
| 02/04/2016 | FIRE SPKLR - FINAL | Partial Approval | 1) System needs to be monitored. Seperate permit required for alarm radio. 2) Need revision submitted for future build out area. 3) Remove pendent heads in future build out area. Plug. 4) Need one upright added in MRI room. 5) Need one upright added in equip room next to MRI room. |