Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T15CM04593
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2015 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/17/2015 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/31/2015 | MECHANICAL - INTERMEDIATE | Denied | ADD WATER HEATER TO PERMIT. REMOVE ANY UNAPPROVED WIRING. CORRECT GAS CONNECTION SIZING. COMPLETE NOTED CORRECTIONS | |
| 08/27/2015 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/27/2015 | MECHANICAL - INTERMEDIATE | Partial Approval | GAS PIPING IS NOT INSTALLED PER PLAN. 1/2" IS UNDERSIZED. STOVE NOT SHOWN. TEST REQUIRED. HORIZONTAL B-VENT IN ATTIC IS NOT ALLOWED (ONCE OFFSET OF MAX 60 DEGREES ALLOWED). PROVIDE CLEARANCES AND SUPPORT, PROPER TERMINATION. COMPLETE NOTED CORRECTIONS. EXPOSE COVERED WORK | |
| 08/07/2015 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/07/2015 | MECHANICAL - INTERMEDIATE | Denied | REMOVE ABANDONED GAS ?? IN WALL AND INSTALL HARD CAP. PROVIDE PLAN OF NEW RTV AND GAS. 1/2" MAY NOT BE PROPERLY SIZED, PIPING IS INCREASED AT ABANDONED WALL FURNACE #2, IN WALL. RACEWAY IS NOT PROPERLY INSTALLED. UNDERGROUND PORTION COVERED PRIOR TO INSPECTION. CO DETECTOR REQUIRED ON RESIDENTIAL. MISSING ROOFTOP RECEPTACLE |