Permit: T15CM04593

Parcel: 12209001B


Addresses:

1701 N VILLAGE DR


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T15CM04593

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2015 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/17/2015 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/31/2015 MECHANICAL - INTERMEDIATE Denied ADD WATER HEATER TO PERMIT. REMOVE ANY UNAPPROVED WIRING. CORRECT GAS CONNECTION SIZING. COMPLETE NOTED CORRECTIONS
08/27/2015 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/27/2015 MECHANICAL - INTERMEDIATE Partial Approval GAS PIPING IS NOT INSTALLED PER PLAN. 1/2" IS UNDERSIZED. STOVE NOT SHOWN. TEST REQUIRED. HORIZONTAL B-VENT IN ATTIC IS NOT ALLOWED (ONCE OFFSET OF MAX 60 DEGREES ALLOWED). PROVIDE CLEARANCES AND SUPPORT, PROPER TERMINATION. COMPLETE NOTED CORRECTIONS. EXPOSE COVERED WORK
08/07/2015 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/07/2015 MECHANICAL - INTERMEDIATE Denied REMOVE ABANDONED GAS ?? IN WALL AND INSTALL HARD CAP. PROVIDE PLAN OF NEW RTV AND GAS. 1/2" MAY NOT BE PROPERLY SIZED, PIPING IS INCREASED AT ABANDONED WALL FURNACE #2, IN WALL. RACEWAY IS NOT PROPERLY INSTALLED. UNDERGROUND PORTION COVERED PRIOR TO INSPECTION. CO DETECTOR REQUIRED ON RESIDENTIAL. MISSING ROOFTOP RECEPTACLE