Inspection History Details
Inspection Status: Approved
Inspection History: TEP CLEARANCE - AM
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2015 | TEP CLEARANCE - AM | Approved | INCR FOR FINAL 1. GROUNDS AND NEUTRALS TO BE SEPERATED 2. WIRES TO SUB PANEL/TO BE #1 TABLE 310.15B3C 3. 2 GROUND RODS TO BE EXPOSED 4. ADDRESS LABLE MISSING 5. CONDENSATION TO HAVE MORE OF A PITCH |