Permit: T15CM04292

Parcel: 11711096D


Addresses:

100 N STONE AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T15CM04292

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2015 PLUMBING - FINAL Approved IVRS - Inspection :*
10/07/2015 PLUMBING - FINAL Not ready for Inspection SUPPORT WTR PIPING ABV COILING
COMPLY WITH PREVIOUS NOTES
FIXTURE MAY NOT BE DOUBLE TRAPPED
08/12/2015 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/12/2015 PLUMBING - FINAL Not ready for Inspection FIXTURE REQUIRES A VENT. PLAN SPECIFIES A 2" WASTE AND VENT. PROVIDE PROPER USE OF DRAINAGE FITTINGS. INSTALL CLEANOUT SHOWN. INSTALL PIPE SUPPORTS. PROVIDE A 6' LADDER
07/01/2015 PLUMBING - FINAL Not ready for Inspection NO PLANS ON SITE PROVIDE ACCESS TO TIE IN. DIRECT CONNECTION TO DWV SYSTEM IS REQUIRED.DRAINAGE FITTINGS ARE REQUIRED PROVIDE PROPER SLOPE CONNECTION TO WALL SHALL BE SEALED. ALL CO JOINTS SHALL BE DEBURRED AND EXCESS FLEX SHALL BE REMOVED