Permit: T15CM04258

Parcel: 14024056A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/30/2015 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/25/2015 ELECTRIC - FINAL Denied 1 PORCH LIGHTS MISSING SAFETY GLOBE
2 ELECTRICAL STUB UP IN YARD BEHIND SHED TO BE PROPERLY TERMINATED
3 WIRING ENTERING SE CORNER OF UNIT NOT TO CODE
4 SMOKE ALARMS REQ IN ALL BED ROOMS AND AREAS ENTERING BEDROOMS
5 EXPOSED ROMEX NOT PERMITTED INCLUDING INSIDE CABINETS BOX'S NOT PROPERLY SECURED
6. ORIGINAL MOBILE IS ON AN UNGROUNDED SYSTEM, REMOVE ALL GROUNDING OUTLETS (2 PRONGS) ROOM ADDITION OK
7 LOAD CENTER IN CLOSET NOT PROPERLY INSTALLED