Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/25/2015 | ELECTRIC - FINAL | Denied | 1 PORCH LIGHTS MISSING SAFETY GLOBE 2 ELECTRICAL STUB UP IN YARD BEHIND SHED TO BE PROPERLY TERMINATED 3 WIRING ENTERING SE CORNER OF UNIT NOT TO CODE 4 SMOKE ALARMS REQ IN ALL BED ROOMS AND AREAS ENTERING BEDROOMS 5 EXPOSED ROMEX NOT PERMITTED INCLUDING INSIDE CABINETS BOX'S NOT PROPERLY SECURED 6. ORIGINAL MOBILE IS ON AN UNGROUNDED SYSTEM, REMOVE ALL GROUNDING OUTLETS (2 PRONGS) ROOM ADDITION OK 7 LOAD CENTER IN CLOSET NOT PROPERLY INSTALLED |