Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2015 | ELECTRIC - RECONNECT | Approved | ||
| 07/06/2015 | ELECTRIC - RECONNECT | Not ready for Inspection | ||
| 07/01/2015 | ELECTRIC - RECONNECT | Denied | 1. THE A/C FEED WIRES ARE NOT TERMINATED IN THE MAIN PANEL AND HAVE EXPOSED WIRE ENDS. 2. THE A/C DISCONNECT BOX, NORTH OF THE MAIN PANEL, IS FALLING OFF THE WALL. 3. THERE IS A #14 WITH A 20 AMP FUSE AND A #12 WIRE WITH A 30 AMP FUSE IN THE SUB-PANEL THAT MUST BE CORRECTED. |
|
| 06/24/2015 | ELECTRIC - RECONNECT | Not ready for Inspection | 1. THERE IS A DOUBLE TAPPED CIRCUIT INTO THE MAIN LUGS THAT MUST BE CORRECTED. 2. CORRECT MIS-MATCHED CIRCUIT WIRES AND FUSE SIZES IN THE INTERIOR SUB-PANEL. |