Permit: T15CM04175

Parcel: 125041320


Addresses:

2101 E 2ND ST #02

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/15/2016 PLUMBING - INTERMEDIATE Approved
03/09/2016 PLUMBING - INTERMEDIATE Denied 1. LEAK AT 2ND FLOOR TOILET WASTE
2. NAIL PROTECTION MUST EXTEND 2"BELOW TOP PLATES AND 2" ABOVE BOTTOM PLATES.
3. ALL DWV LINES MUST BE PROPERLY SUPPORTED.
4. STUDOR VENT IS APPROVED FOR KITCHEN SINK. (IF IT WILL TERMINATE IN WALL, IT MUST HAVE ACCESS PANEL.)