Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/17/2015 | ELECTRIC - FINAL | Denied | 1. PLASTIC BUSHING FOR WIRES ON BACK OF PANEL MISSING 2. RISER BRACING MISSING 3. 2 GROUND RODS MISSING 4. NEUTRALS AND GROUNDS NOT TO BE SEPERATED AT SERVICE |