Permit: T15CM03828

Parcel: 132101300

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/16/2015 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/12/2015 ELECTRIC - SERVICE UPGRADE Denied 1. 50 AMP CRT BREAKER TO BIG FOR #8 AL WIRE
2. BOND WATER LINE
3. I.D CERCUIT BREAKERS
4. 1/4" MIN HARDWARE FOR RISER CONDUIT SUPPORT
IRC-NEC