Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2015 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/12/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. 50 AMP CRT BREAKER TO BIG FOR #8 AL WIRE 2. BOND WATER LINE 3. I.D CERCUIT BREAKERS 4. 1/4" MIN HARDWARE FOR RISER CONDUIT SUPPORT IRC-NEC |