Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T15CM03793
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2016 | FRAMING | Approved | ||
| 08/23/2016 | FRAMING | Not ready for Inspection | 1. SOME ANCHOR BOLTS MISSING NUT AND WASHER. 2. SOME ANCHOR BOLTS ARE MISSING. (WITHIN 12" OF PLATE ENDS AND SPLICES.) 3. FIRE BLOCKING IS REQUIRED AT ALL CEILINGS AND DROPS (SOFFITS) 4. FIRE STOP ALL TOP PLATE PENETRATIONS. |
|
| 08/08/2016 | FRAMING | Partial Approval | CLASSROOM AREA ( INTERIOR AND EXTERIOR WALLS) |