Permit: T15CM03777

Parcel: 113042820


Addresses:

942 E HALCYON RD

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/08/2015 ELECTRIC - RECONNECT Denied 1. PULL DOUBLE TAPPED WIRES FROM MAIN PANEL LUGS.
2. SEPERATE DOUBLE TAPPED WIRES INTO 1 BREAKER IN SUB-PANEL.
3. SEPERATE NEUTRALS AND GROUNDS IN SUB-PANEL.
06/08/2015 ELECTRIC - RECONNECT Approved