Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T15CM03757

Parcel: 136332520


Addresses:

2742 S BEECHWOOD AV


Inspection Status: Denied

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T15CM03757

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
08/21/2015 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/21/2015 MECHANICAL - INTERMEDIATE Denied PROVIDE MIN 2" DUCT LINER IN EXPOSED DUCT. PROVIDE A SEDIMENT TRAP AT GAS LINE TOFURNACE. THIS IS NOT A LIKE-FOR-LIKE REPLACEMENT. PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW A/C ON ROOF. DO NOT USE INDOOR ELEC FITTINGS ON OUTDOOR CONDUIT. PROVIDE THE RQUIRED SERVICE RECEPTACLE ON ROOF. BLOCK AND CLAMP PVC EVERY 4' AND PAINT W/ LATEX PAINT. PROVIDE A ROOF JACK AT ELEC PENETRATION IN ROOF. NEED TO SEE ANY NEW DUCT INSIDE THE HOUSE. IT APPEARS A STUD MAY HAVE BEEN CUT FROM A BEARING WALL UNDER THE A/C UNIT. EXPOSE FRAMING FOR INSPECTION