Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T15CM03757
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2015 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/21/2015 | MECHANICAL - INTERMEDIATE | Denied | PROVIDE MIN 2" DUCT LINER IN EXPOSED DUCT. PROVIDE A SEDIMENT TRAP AT GAS LINE TOFURNACE. THIS IS NOT A LIKE-FOR-LIKE REPLACEMENT. PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW A/C ON ROOF. DO NOT USE INDOOR ELEC FITTINGS ON OUTDOOR CONDUIT. PROVIDE THE RQUIRED SERVICE RECEPTACLE ON ROOF. BLOCK AND CLAMP PVC EVERY 4' AND PAINT W/ LATEX PAINT. PROVIDE A ROOF JACK AT ELEC PENETRATION IN ROOF. NEED TO SEE ANY NEW DUCT INSIDE THE HOUSE. IT APPEARS A STUD MAY HAVE BEEN CUT FROM A BEARING WALL UNDER THE A/C UNIT. EXPOSE FRAMING FOR INSPECTION |