Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2015 | FIRE - FINAL | Approved | ||
| 12/14/2015 | FIRE - FINAL | Denied | 1. Move all stock down 18 inches away from sprinkler heads 2. Call in fire alarm final T15BU01219 3. Need to test all emergency lights 4. Need two 2A-10BC fire extinguishers 5. Fire Hydrant front of building in parking lot has an O.O.S. ring on it when I tested the hydrant it was off need to get it in service. |
|
| 12/11/2015 | FIRE - FINAL | Partial Approval | duct detector number 1 was not shutting down the Correct ventilation unit. ( general contractor stated that the AC technician wired the detector to the wrong vents). Check to see that DD1 shuts down the correct unit. Already smoked the dectector and it worked...ok to use test button. |
|
| 12/09/2015 | FIRE - FINAL | Partial Approval | Ceiling Tiles are not in place, duct detectors did not shut down unit. OKAY for TCO to stock only but no public until reinspection fees are paid, hood system approved and final inspection for this permit is complete._Ken B |