Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | Addition of 23 LF of 4 " C900. Pressure tested at 200 psi for more than 2 hrs. Was pressured up at 10 AM - read at 2:52 PM |