Permit: T15CM03602

Parcel: 13409018F


Addresses:

8616 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/03/2015 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/03/2015 MECHANICAL - ABOVE CEILING Approved REVISE PLANS TO SHOW ADDED DCUT SMOKE DETECTORS AND RELATED WIRING OR REMOVE. DETECTORS TO BE INSTALLED IN RETURN NOT SUPPLY. WIRE INTO ALARM PANEL. OK FOR PARTIAL CEILING TILES. LEAVE OUT IN AREAS TO SEE NEW CONDENSATE DRAIN
07/28/2015 MECHANICAL - ABOVE CEILING Partial Approval OK TO SHEET ROCK
07/10/2015 MECHANICAL - ABOVE CEILING Partial Approval SEALED DUCT JOINTS OK TO INSULATE
OK TO BACK FILL PLUMBING AND POUR