Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/22/2015 | MECHANICAL - FINAL | Not ready for Inspection | 1. SEAL TILE AT C.U. REQUIRES APPROVED FITTINGS AT CABINET 2. LINE SET INSULATION NOT PROPERLY COATED 3. ELECTRICAL TAPE NOT APPROVED ON EXTERIOR USE U.U RATED WRAPS 4. LINE SET PENETRATION REQUIRES ROOF TACK 5. POWER CORD NOT CLAMPED 6. NEW WATER HEATER REQUIRES PERMIT 7 W/A T&E NOT PROPERLY TERMINATED 8. AN APPLIANCE CAN NOT BE INSTALLED WHERE ONE HAS TO BE REMOVED TO REPLACE ANOTHER 9. WATER HEATER CAN BE APPROVED THIS PERMIT. |