Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T15CM03318

Parcel: 131030970


Addresses:

5202 E ANDREW ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/11/2015 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/11/2015 ELECTRIC - FINAL Denied SEE LISTING INFO INSIDE PANEL ON COVER...NO LOAD CONDUCTORS TO EXIT THROUGH TOP OF PANEL ENCLOSURE. PER LISTING, RE-ROUTE LOAD CIRCUITS AND CAP TOP KNOCKOUTS WITH AN APPROVED PLUG RATED FOR OUTDOOR USE