Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2015 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2015 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/05/2015 | BUILDING - FINAL | Denied | 1. MAIN DISCONNECT TWO WIRES ON ONE LUG AND LUG TO BE ANCHORED 2. GROUND RODS MISSING 3. NEUTRAL TO BE BONDED IN LOAD CENTER OR SUBPANEL 4. A/C DISCONNECT NOT TO PRINT 5. LINESIDE TAP NOT TO PRINT 6. NO LABELS |