Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM03203
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2015 | FIRE - FINAL | Approved | ||
07/06/2015 | FIRE - FINAL | Denied | 1. Need Fire extinguishers install 1 for every 1500 sq. inch of building space and the travel distance cannot be more than 75 feet must be min 2A - 10 BC type. 2. Repair or replace the exit over the front door failed during testing 3. Repair or replace the emergency light by front door and restroom failed when tested. 4. Re-label electrical panel for what each breaker is used for 5. Add 3 inch address number on rear door. 6. Need annual and 5 year sprinkler inspection completed field notice given. 7. Need all ceiling tiles in place cannot have any openings because of sprinkler coverage. NFPA 13 does not allow both uprights and pendants exposed to each other. 8. Remove orange color packaging protectors of sprinkler heads. |