Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2015 | FIRE SPKLR - FINAL | Approved | ||
| 07/06/2015 | FIRE SPKLR - FINAL | Denied | 1. Need annual and 5 year sprinkler inspection completed field notice given. 2. Need all ceiling tiles in place cannot have any openings because of sprinkler coverage. NFPA 13 does not allow both uprights and pendants exposed to each other. 3. Remove orange color packaging protectors of sprinkler heads. |