Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T15CM03073
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/05/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/10/2015 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/02/2015 | ELECTRIC - FINAL | Denied | 1. USE APPROVED J BOX SIZED PER CODE FOR FEEDERS, EXISTING PANEL NOT LISTED OR SIZED CORRECTLY ART 314 NEC 2. ALL FEEDERS AND BRANCH CIRCUITS IN THE SAME ENCLOSURE OR RACEWAY ORIGINATING FROM DIFFERENT SYSTEMS OR SERVICE MAINSSHALL BE TAGGED OR LABELED AS TO IDENTIFY THEIR LOADS 3. FEEDER OF DEFFERENT SOURCES AND LOADS NOT TO FEED THRU OTHER TENANTS AND SERVICE EQUIP OR PANELS NEC 312.8 4. GROUNDS AND NEUTRALS TO BE ISOLATED IN SUB PANELS PER 250 NEC 5. IDENTIFY OR LABEL SUB PANELS 6. PLUG ALL UNUSED OPENING IN ENCLOSURES 7. COVER AND SUPPORT GROUND TO STRUCTURE BELOW SERVICE EQUIP |