Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T15CM03073

Parcel: 11714354B


Addresses:

570 S MAIN AV #01


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T15CM03073

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2015 ELECTRIC - SERVICE UPGRADE Approved PER ELEC FINAL
06/08/2015 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
06/08/2015 ELECTRIC - SERVICE UPGRADE Partial Approval SEE NOTE #4 DATED 06/02/15L. ALL OTHER NOTES OK
06/02/2015 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/02/2015 ELECTRIC - SERVICE UPGRADE Denied 1. GROUND RODS TO BE BELOW GROUND LEVEL
2. WIRE IN RISER NOT TO CODE; TABLE 310, 15 B 16
3. RISER TO BE (LISTED BRACED), BONDED, AND TWO 2-HOLE STRAPS TO BE INSTALLED
4.LOAD SIDE TO BE INSTALLED
5. ADDRESS LABEL FOR EACH METER MISSING
06/02/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection ANOTHER FAILED INSPECTION WILL REQUIRE A RE-FEE
06/01/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
05/28/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
05/28/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection CONTRACTOR CANCELED BY PHONE
05/27/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*