08/07/2015 | ELECTRIC - SERVICE UPGRADE | Approved | PER ELEC FINAL | |
06/08/2015 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
06/08/2015 | ELECTRIC - SERVICE UPGRADE | Partial Approval | SEE NOTE #4 DATED 06/02/15L. ALL OTHER NOTES OK | |
06/02/2015 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/02/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. GROUND RODS TO BE BELOW GROUND LEVEL 2. WIRE IN RISER NOT TO CODE; TABLE 310, 15 B 16 3. RISER TO BE (LISTED BRACED), BONDED, AND TWO 2-HOLE STRAPS TO BE INSTALLED 4.LOAD SIDE TO BE INSTALLED 5. ADDRESS LABEL FOR EACH METER MISSING |
|
06/02/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | ANOTHER FAILED INSPECTION WILL REQUIRE A RE-FEE | |
06/01/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
05/28/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
05/28/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | CONTRACTOR CANCELED BY PHONE | |
05/27/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |