Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/15/2015 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 07/02/2015 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
1.25" drain is too small for 8 .5" drain lines. Pipe last 2 separately. ok for rock. |
| 06/30/2015 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
POST CORRECT SUIT NUMBER. PROVIDE DOCUMENTATION TO SUPPORT ANY CHANGES. DRAIN PIPING MAY NOT BE RESTRICTED, AND MUST BE PROPERLY SIZED. |