Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/26/2015 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/26/2015 | MECHANICAL - FINAL | Partial Approval | ALL MECHANICAL WORK IS NOW COMPLETED AND INSPECTED. CANNOT CLOSE MECH PERMIT UNTIL A REMODEL PERMIT HAS BEEN OBTAINED AS PER VIOLATION NOTICE | |
| 08/19/2015 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/19/2015 | MECHANICAL - FINAL | Denied | TERMINATE CONDENSATE TO THE GROUND. COAT EXPOSED ARMAFLEX. SERVICE RECEPT CANNOT BE JUMPERED FROM A/C POWER. PROVIDE DOUBLE WALL VENT FOR FURNACE WITH AN APPROVED CAOP. SINGLE WALL VENT NEEDS 6" CLEARANCE FROM ARMAFLEX. PROVIDE AN OVERFLOW SENSOR. PROVIDE A STAND PIPE IN CONDENSATE VENT. PROVIDE A ROMEX CONNECTOR AT FURNACE |