Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T15CM02792
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2016 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2015 | PLUMBING - FINAL | Partial Approval | ISULATE DUCTS ..MIN R8NEED T&P DRAIN VALVE AT WATER HEATER PROVIDE 1/8" SLOPE ON CONDENSATE DRAIN |
|
| 06/24/2015 | PLUMBING - FINAL | Denied | UNIT 12 AND 13 RELOCATE WATER HEATER DISCONNECT TO ALLOW PROPER ACCCESS AND PROVIDE A BETTER CONNECTION AT FITTING. UNIT 11 PROVIDE A T AND P DRAIN.. TIGHTEN LOOSE FITTINGS AT AC UNITS AND DISCONECTS ALL UNITSS PROVIDE MIN R-8 2" DUCT LINES IN EXPOSED DUCT ON ROOF PROVIDE 1/8" PER FT SLOPE ON ALL SECTIONS OF CONDENSATE DRAIN AND SUPPORT EVERY4 FEET. | |
| 06/22/2015 | PLUMBING - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |