Permit: T15CM02778

Parcel: 12407185A


Addresses:

721 E 12TH ST


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T15CM02778

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2016 FIRE - FINAL Approved Last inspector required fire alarm to be replaced or proof be shown as to why it could be removed. Fire Alarm System was replaced/modified per permit number # T15BU00911.
Fire Alarm System passed test on 1/28/16, but Alarm contractor must submit the as-builds showing added appliances and changes to zones before that permit will be approved and finaled.
06/08/2015 FIRE - FINAL Denied 1. Need to either replace fire alarm system or prove why its not needed.
05/28/2015 FIRE - FINAL Denied 1. Need annual fire sprinkler inspection completed last inspection on file shows 02.02.2012.
2. Gauges are bad - both where changed out during this inspection
FDC caps need replacing
3. Need new calculation plate on riser
4. Need new signage on riser -i.e. main drain, main shut off
5. Label FDC with the following: "FDC" 6 inch red letters white background