Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM02778
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2016 | FIRE - FINAL | Approved | Last inspector required fire alarm to be replaced or proof be shown as to why it could be removed. Fire Alarm System was replaced/modified per permit number # T15BU00911. Fire Alarm System passed test on 1/28/16, but Alarm contractor must submit the as-builds showing added appliances and changes to zones before that permit will be approved and finaled. |
|
06/08/2015 | FIRE - FINAL | Denied | 1. Need to either replace fire alarm system or prove why its not needed. | |
05/28/2015 | FIRE - FINAL | Denied | 1. Need annual fire sprinkler inspection completed last inspection on file shows 02.02.2012. 2. Gauges are bad - both where changed out during this inspection FDC caps need replacing 3. Need new calculation plate on riser 4. Need new signage on riser -i.e. main drain, main shut off 5. Label FDC with the following: "FDC" 6 inch red letters white background |