Permit: T15CM02778

Parcel: 12407185A


Addresses:

721 E 12TH ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
06/08/2015 FIRE SPKLR - FINAL Approved
05/28/2015 FIRE SPKLR - FINAL Denied 1. Need annual fire sprinkler inspection completed last inspection on file shows 02.02.2012.
2. Gauges are bad - both where changed out during this inspection
FDC caps need replacing
3. Need new calculation plate on riser
4. Need new signage on riser -i.e. main drain, main shut off
5. Label FDC with the following: "FDC" 6 inch red letters white background