Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2016 | BUILDING - FINAL | Approved | OK TO OCCUPY. | |
| 10/19/2016 | BUILDING - FINAL | Partial Approval | 1/2" ID X 18" GAS FLEX NOT ADEQUATE FOR 180,000 BTU. PROVIDE A GFI RECEPTACLE AT INJECTOR PUMP. PAIONT EXPOSED PVC WITH LATEX PAINT. WHITE WIRE NOT ALLOWED ON A 240 V. SYSTEM. |