Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/22/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/22/2015 | ELECTRIC - FINAL | Denied | 1. SUBPANEL AND METER IN BATHROOM NOT TO CODE 245 AND 110.26 3' WORKING CLEARANCE MISSING AND 230.72.2 SERVICE DISCONNECTION MEANS SHALL NOT BE INSTALLED IN BATHROOMS AND WHY HAVE TWO METERS? 2. LAUNDRY ROOM WASHER AND DRYER OUTLETS MISSING COVER PLATES |