Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2016 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/28/2016 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A VENT FOR THE MASTER BATH LAVATORY DRAIN THAT RISES VERTICAL TO 42 INCHES AFF AND REVENT INTO THE 2 INCH VTR. 2- RETEST SANITARY SYSTEM. * |
|
| 07/26/2016 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A VENT FOR THE LAVATORY DRAIN IN MASTER BATH. 2- SHALL PROVIDE THE REQUIRED SAFTEY PLATES THAT EXTEND 2 INCHES ABOVE SOLE PLATES AND BELOW THE TOP PLATES. REFERENCE SECTION 305.6 2012 IPC. 3- SHALL USE A SAN TEE FOR THE TRAP ARM AT A.W. BOX. 902.2 IPC. 4- NOTE. SHALL PROVIDE HAMMER ARRESTORS FOR A.W. BOX. THEY MAT BE LOCATED IN THE WASHER BOX OR PROVIDE THE ADD ON EXTERIORS ARRESTORS AT TIME OF FINAL INSPECTION. 5- RE TEST THE DWV SYSTEM. * |