Permit: T15CM02489

Parcel: 128100810

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T15CM02489

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2015 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
07/10/2015 PLUMBING - ROUGH, SOIL Denied REFEE ASSESSED FAILURE TO COMPLY WITH PREVIOUS INSPECTION NOTES
not installed per plan 150. same corrections each dry vent shall rise vertically as shown on plan. a sanitary tee may not be used in a horizontal position. contrator shall pay reinspection fee
07/07/2015 PLUMBING - ROUGH, SOIL Denied PROVIDE PROPER USE OF DIRECTION DRAINAGE FITTINGS
PROVIDE CLEANOUTS SIZED PER PLAN
06/25/2015 PLUMBING - ROUGH, SOIL Denied OWNER SAYS CHAERS AREA A PUMPING DISCHARGE WHICH REQUIRES FLOOR SINKS REVISE PAN TO SHOWER OR INSTALL PER PLAN IF NO PUMP. EACH FIXTURE REQUIRES A DRY VENT PER PLAN
06/23/2015 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOT INSTALLED PER PLAN; DIRECT CONNECTIONS SHOWN, FULL SZED CLEANOUTS. DRY VENT SHALL RISE VERTICALLY TO 6" AVOVE FLOOD LEVEL PRIOR TO OFFSET. SUPPORT/SHADE PIPING.