Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T15CM02489
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2015 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
07/10/2015 | PLUMBING - ROUGH, SOIL | Denied | REFEE ASSESSED FAILURE TO COMPLY WITH PREVIOUS INSPECTION NOTES not installed per plan 150. same corrections each dry vent shall rise vertically as shown on plan. a sanitary tee may not be used in a horizontal position. contrator shall pay reinspection fee |
|
07/07/2015 | PLUMBING - ROUGH, SOIL | Denied | PROVIDE PROPER USE OF DIRECTION DRAINAGE FITTINGS PROVIDE CLEANOUTS SIZED PER PLAN |
|
06/25/2015 | PLUMBING - ROUGH, SOIL | Denied | OWNER SAYS CHAERS AREA A PUMPING DISCHARGE WHICH REQUIRES FLOOR SINKS REVISE PAN TO SHOWER OR INSTALL PER PLAN IF NO PUMP. EACH FIXTURE REQUIRES A DRY VENT PER PLAN | |