Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T15CM02489
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2015 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/30/2015 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/25/2015 | BUILDING - FINAL | Not ready for Inspection | PROVIDE A 1" AIR GAP AT SPA DRAINS AND WATER HEATER RELIEF DRAIN. REMOVE CHECK VALVE FROM TEMPERATURE AND PRESSURE RELIEF DRAIN. | |
11/17/2015 | BUILDING - FINAL | Not ready for Inspection | PROVIDE ANSI LISTING FOR WHILPOOL SPA'S. INSTALL WATER HEATER AS SHOWN ON PLAN, PROVIDE AIR GAP AT RELIEF DRAIN. PROVIDE WATER SYSTEM STERILIZATION. PROVIDE AIR BALANCE REPORT. INSTALL CODE APPROVED CLEAN-OUT FITTINGS AS PREVIOUSLY NOTED. INSTALL DOME STAINERS IN FLOOR SINKS. CAULK FIXTURES. DISCONNECT AND INTERLOCK SHOWN FOR EXHAUST FAN. WATER HAMMER ARRESTORS SHOWN ON WASHER BOX DETAIL. ( CALL FOR ALL REQUIRED INSPECTIONS LISTED ON YOUR PERMIT CARD. FIRE FINAL NEEDED.)PROVIDE ANSI LISTING FOR WHILPOOL SPA'S. INSTALL WATER HEATER AS SHOWN ON PLAN, PROVIDE AIR GAP AT RELIEF DRAIN. PROVIDE WATER SYSTEM STERILIZATION. PROVIDE AIR BALANCE REPORT. INSTALL CODE APPROVED CLEAN-OUT FITTINGS AS PREVIOUSLY NOTED. INSTALL DOME STAINERS IN FLOOR SINKS. CAULK FIXTURES. DISCONNECT AND INTERLOCK SHOWN FOR EXHAUST FAN. WATER HAMMER ARRESTORS SHOWN ON WASHER BOX DETAIL. ( CALL FOR ALL REQUIRED INSPECTIONS LISTED ON YOUR PERMIT CARD. FIRE FINAL NEEDED.) |