Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T15CM02465
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2015 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 04/22/2015 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 04/20/2015 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/20/2015 | ELECTRIC - RECONNECT | Denied | A WATER PIPE BOND IS NOT APPROVED FOR USE AS A GROUNDING ELECTRODE SYSTEM. PROVIDE 2-8' GROUND RODS MIN 6' APART | |
| 04/16/2015 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/16/2015 | ELECTRIC - RECONNECT | Denied | THE GROUNDING ELECTRODE CONDUCTORS HAVE BEEN VANDALIZED. PLEASE PROVIDE A GROUNDING ELECTRODE SYSTEM AND REBOND WATER PIPING |