Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2015 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* BE ADVISED YOU SHOULD TRY TO MAKE THE EXPOSED COPPER WIRE BLEND INTO THE BLDG BY PAINT OR SOME TYPE OF COVER TO DETOUR VANDELS FROM TAKING THE WIRE |
|
| 06/09/2015 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/09/2015 | ELECTRIC - TEMPORARY SERVICE | Denied | - NEW SERVICE GROUNDING TO BE TIED IN WITH EXISTING SERVICE GEC. GROUNDING TO BE COMMON GROUNDING ELECTRODE SYSTEM FOR MULTIPLE SERVICES LOCATED ON SAME BLDG OR STRUCTURE. PER 250.28 NEC - FUSES MISSING ON NEW SERVICE - BE ADVISED THAT EXISTING SERVICE GROUND HAS BEEN CUT (VANDALIZED) AND WILL NEED TO BE REPLACED ASAP AS THIS IS A POTENTIAL LIFE SAFETY ISSUE |