Inspection History: FIRE - FINAL
Permit Number - T15CM02145
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2015 | FIRE - FINAL | Approved | ||
05/06/2015 | FIRE - FINAL | Denied | 1. Need sprinkler head escutcheons in place 2. Remove falling insulation off of sprinkler heads in mezz area 2nd floor 3. Mount fire extingushers on wall |
|
04/17/2015 | FIRE - FINAL | Denied | BUSINESS WANTS TO OPEN MERCHANT SIDE BEFORE THE BACK RECEIVING AND STOCK AREAS ARE FINISHED WITH REPAIRS. THEY WOULD LIKE TO MEET WITH BUILDING AND FIRE TO DISCUSS A TEMP C OF O FOR THE MERCHANT SECTION AND HAVING A SECOND PHASE OF REPAIR. WILL NEED TO: 1. CLOSE UP OPENINGS IN THE FIRE RATED CONSTRUCTION ABOVE THE DROP CEILING ON THE WEST WALL AND IN THE WALL OF REST ROOM, OTHER WALLS ETC. 2. NEED TEST OF ALRM SYSTEM AFTER FIRE TO DETERMINE OPERATIONAL AND REPORTING 3. ALL BACK UP EXIT LIGHTING AND EMERGENCY LIGHTING SHALL WORK ON POWER SHUT DOWN. 4. EXTINGUISHERS SHALL BE EVERY 75 FEET TRAVEL DISTANCE 5. APPROVED FIRE SPRINKLER SYSTEM FINAL AFTER REPAIRS BY NAVERETTE & CURRENT PASSING TEST WITH 5 YR CHECK VALVE VERIFIED. |