Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2015 | FIRE - FINAL | Approved | PER PHONE CONVERSATION AND INSPECTION FORM | |
| 06/15/2015 | FIRE - FINAL | Denied | 1. Need to secure the OS&Y on the riser with a chain and padlock 2. Remove the outlet that is on the fire bell circuit, the fire bell needs a dedicated circuit can't share with any else. |
|
| 06/10/2015 | FIRE - FINAL | Partial Approval | 1. Sprinkler system report needed with 5 yr chech valve report 2. replace missing fdc cap 3. provide 36 inches clear path to the FDC's 4. Need FDC sign on exterior of building over connections. 5. sprinkler head is too close to the wall in hallway 6. 1 painted sprinkler head in restroom |