Permit: T15CM02097

Parcel: 13013044B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
06/16/2015 FIRE - FINAL Approved PER PHONE CONVERSATION AND INSPECTION FORM
06/15/2015 FIRE - FINAL Denied 1. Need to secure the OS&Y on the riser with a chain and padlock
2. Remove the outlet that is on the fire bell circuit, the fire bell needs a dedicated circuit can't share with any else.
06/10/2015 FIRE - FINAL Partial Approval 1. Sprinkler system report needed with 5 yr chech valve report
2. replace missing fdc cap
3. provide 36 inches clear path to the FDC's
4. Need FDC sign on exterior of building over connections.
5. sprinkler head is too close to the wall in hallway
6. 1 painted sprinkler head in restroom