Permit: T15CM01864

Parcel: 136416830

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/24/2015 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/23/2015 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/23/2015 PLUMBING - INTERMEDIATE Denied SECURE HOSE BIB BACK WALL. SECURE TUBING IN STUD WALLS; USE ISOLATORS OR FOAM. SECURE COPPER STUBOUTS. REMOVE EXCESS FLUX. REPLACE GAS FLEX AT WH. ALSO, PROVIDE GALV OR BRASS NIPPLES. REPLACE DAMAGED VENT CONNECTOR AT WH DRAFT HOOD. HOSE BIB VACUUM BREAKERS & WASHER BOX WATER HAMMER ARRESTORS REQUIRED.
(NOTE: LAUNDRY ROOM FLOOR DRAIN COVERED W/ TILE. REQUIRES APPROVED PLUG OR CAP. KEEP OPEN DWV PIPES CAPPED FOR SAFETY DURING CONSTRUCTION)