Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/07/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/07/2015 | ELECTRIC - FINAL | Denied | 1. GROUND #4 HAVE TO BE CONTINUOUS 2. SECURE #4 TO BUILDING 3. UNABLE TO LOCATE BONDING 4. BOND GAS & WATER TO SERVICE PANEL GROUND BUSS |
|
| 04/03/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/16/2015 | ELECTRIC - FINAL | Denied | TRIED TO LEAVE MSG 10:45 AM MAILBX FULL 1. MAIN SERVICE NOT GROUNDED PROVIDE GROUND ROD SYSTEM 2. HAZARDOUS WIRING @ 30 AMP CIRCUIT 3. WHITE HOT LEAD @ 50 AMP CIRCUIT TO BE RED OR BLK TAPE OK 4. NO ACCESS TO INTERIOR 5. ALL ADDITIONS SHOULD BE ON RECORD |