Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/04/2015 |
ELECTRIC - FINAL |
|
Approved |
|
| 08/20/2015 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 08/20/2015 |
ELECTRIC - FINAL |
|
Partial Approval |
LIVINGROOM AND ENTRY NEEDS ARC FAULT BREAKERS. PROVIDE TAMPER RECEPTACLES AS PER 2012 IRC. MARK A/C UNIT DATA PLATE W/ PROPER HEAT STRIP AND FUSE ACCORDINGLY. USE PURPLE PRIMER ON PVC FITTINGS AND SUPPORT EVERY 4' AND PAINT EXPOSED PVC |