Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T15CM01606
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2015 | FRAMING | Approved | IVRS - Inspection :* | |
05/06/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
05/05/2015 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
05/01/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
04/30/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
04/30/2015 | FRAMING | Partial Approval | 1. PROVIDE FIRE SPRIKLER INSPECTION PRIOR TO SHEETROCK 2. REGISTER CANS TO BE FRAMED ON THREE SIDES 3. PROVIDE ACCESS PANELS FOR ALL VALVES ABOVE HARD LIDS 4. COMPLETE BACKING AT ADA GRAB BARS 5.COMPLETE CONDENSATE 6.COMPLETE T & P WITH PITCH 7.THIS INSPECTION IS FOREAST RESTROOMS ONLY |
|
04/27/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
04/27/2015 | FRAMING | Partial Approval | BACK OF HOUSE OK | |
04/22/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
04/22/2015 | FRAMING | Partial Approval | FRAMING AND ELECTRICAL INTERMEDIATE OK, EXCLUDING BACK OF HOUSE |